Tech Tip #8
Control of Air Conditioners
Control the contactor for the compressor by breaking the low-voltage
signal from the thermostat. Be sure to program a minimum OFF-TIME on the
relay of at least 5 minutes to prevent short cycling of the compressor,
and a minimum ON-TIME of 6 to 9 minutes for desired comfort level. In most
cases, the fan should not be controlled - it should run when the compressor
is shed.

Click on image for a close-up view
Hook-up
1. Refer to the A/C schematic and locate the wire from the thermostat
that signals the compressor to operate (not the common return line).
2. Run a 2-conductor, 18-gauge wire from the control unit to the outdoor
unit and interrupt the wire locaeted in Step 1 above.
3. Program a minimum OFF-TIME on the relay of at least 5 minutes to prevent
short cycling of the compressor. Program a minimum ON-TIME of 6 to 9 minutes
for desired comfort level.
|