|
Tech Tip #7
Control of Electric Boilers
Electric boilers contain several 5 KW elements that are usually staged
to turn on and off with timed sequencers. You must break each element individually
with a separate relay with line voltage control in order to control the
elements.
To break the elements separately, you must have the control unit close
enough to the boiler to make wiring with the line voltage economical, or
you must use an Energy Sentry® Remote Relay Unit (see Tech
Tip #10 for information).

Click on image for a close-up view
Hook-up
1. Turn breaker(s) to the boiler OFF.
2. Mount Remote Relay Unit (if used) near the boiler to be controlled.
Or, if the boiler is close enough to run conduit of flex between the main
control unit and the boiler, make the connections directly at the control
unit itself.
3. Interrupt the wires that feed each 5 KW element and wire them throught
the relays. Use one element per relay if possible (four elements are typical).
Use two elements per relay if necessary (five or six elements are typical).
4. Hook up the Remote Relay Unit to the control unit using the instructions
provided.
5. With electric furnaces, the load control strategy should be programmed
as "fixed priority," in the same order as the loads are controlled
by the sequencer. Refer to Tech Tip #15
for
information about load control strategy.
|