|
Tech Tip #6
Control of Electric Furnaces
Most residential furnaces have between 10 KW and 30 KW of resistance
heat installed. Usually the total wattage is divided into 5 KW elements,
staged by timing relays controlled by a "sequencer." These relays
allow some or all of the heat to come on, depending on the model or the
controls.
The Energy Sentry can control the stages by breaking the low-voltage
signals or by controlling each 5 KW element individually via line voltage.

Hook-up (Low-Voltage Control)
1. Refer to the diagram on the furnace and locate the sequencing relays
for the heating elements.
2. For a 20 KW furnace (or 2 relays), run a 4-conductor, 10-gauge wire
from the control unit to the furnace. For a 30 KW furnace (or 3-relays),
run 6-conductor cable.
3. Interrupt the coil wire of the "last-on" sequencing relay
in the furnace and wire it through the control unit relay. Most sequencing
relays are double pole; thus, 10 KW of heat is controlled by each relay
of the furnace.
4. Repeat Step 3 for the "next-on" sequencing relay and wire
it through the next higher priority relay of the control unit.
5. With electric furnaces, the load control strategy should be programmed
as "fixed priority," in the same order as the loads are controlled
by the sequencer. Refer to Tech Tip #13 for
information about load control strategy.

Individual Element Control
1. Turn breaker OFF at the furnace.
2. If a Remote Relay Unit is required, mount it in a suitable place on
or near the furnace housing. If the furnace is close enough to run conduit
or flex between the main control unit and the furnace, make the connections
directly at the control unit itself.
3. Interrupt the 1-gauge wires that feed each element and rewire them
throught he control unit relay. Use one element per relay if possible (four
elements typical). Use two elements per relay if necessary (five or six
elements typical).
4. Follow the directions that come with the Remote Relay Unit to hook
it to the main control unit. See Tech Tip #10
for information about the Remote Relay Unit.
5. With electric furnaces, the load control strategy should be programmed
as "fixed priority," in the same order as the loads are controlled
by the sequencer. Refer to Tech Tip #13 for
more information on load control strategy.
Caution
Because most sequencing relays have built-in time delays of an unknown
length, it is best to use the "individual element" control method,
if possible, for consistently good results.
Control of Heat Pump:
Example of Priority Hookups
4-Relay Models
Control of Heat Low Voltage
|
Last
Shed |
24-hour control |
First Shed |
| Relay |
1 |
2 |
3 |
4 |
| Load |
Dryer |
Water
Heater |
10KW Heat |
10KW
Heat |
8-Relay Models or 4-Relay Model with Remote
Relay Unit
Control of Heat Individual Elements
|
Last
Shed |
24-hour control |
First Shed |
| Relay |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
| Load A |
Dryer |
Water
Heater |
5KW
Heat |
5KW
Heat |
5KW
Heat |
5KW
Heat |
5KW
Heat |
5KW
Heat |
| |
|
|
|__________________________________________|
To Remote Relay Unit |
| |
|
|
|___________________________|
20KW Furnaces |
|
|
Caution
In extremely cold regions, it may be necessary to leave the first 5-KW
element uncontrolled to avoid having the blower run with all the elements
turned off. Another alternative is to connect the first 5-KW element to
the highest priority control point, thereby making it the last shed.
|