|
Tech Tip #5
Control of Heat Pumps
Two separate loads in heat pumps usually must be controlled: The compressor
and the backup (auxiliary) heat. Generally, the compressor is controlled by breaking
the low-voltage signal from the thermostat, usually the Yellow (Y) wire. The backup heat
is controlled by either breaking the low-voltage signals from the thermostat,
usually the White (W) wire and the defrost
relay, or by controlling the individual 5 KW elements inside the air handler
unit.
Once you have completed several jobs, connecting heat pumps to demand
controllers is usually simple and straightforward. Take your time on the
first job or two to read the directions. Call the factory for assistance
if necessary. An improper hookup will cause many callbacks and a loss
of your time, money and customer satisfaction.
These directions are only a general guide to the proper hookup of heat
pumps. Because there are so many brands in the field, each installation
may be slightly different. Please take time to read the manufacturer's diagrams
carefully. A good reference guide is the Honeywell Multistage thermostat
Manual, P/N 60-2116-3. for basic background information on heat pumps, refer
to the Honeywell Heat Pump Controls Manual, P/N 71-97735.

Click on image for a close-up view
Hook-up (Compressor)
1. Refer to the schematic on the compressor unit. Locate the low-voltage wire
(Yellow wire or "Y" terminal) from
the thermostat that signals the compressor relay to operate.
2. Run a 2-conductor, 18-gauge wire from the control relay to the
point where the thermostat wire ties the signal to the compressor contactor.
This point can usually be found in the air handler unit. If not, you will
find it in the outdoor condensing (compressor) unit.
3. Interrupt the signal found in Step 2 with the 2-conductor wire. Connect
the other end of the wire to the control relay.
4. Be sure to program the relay with a minimum OFF-TIME of at least 5
minutes to prevent short cycling of the compressor. Be sure to program a
minimum ON-TIME of 6 to 9 minutes to maintain desired comfort. If the
compressor contains its own internal short-cycle protection, the minimum Off
Time may be set to zero (0).
Caution
In extremely cold areas, compressor control is discouraged because of the
inefficiency that results from frequent starting and stopping the compressor.

Click on image for a close-up view
Hookup Auxiliary Heat (Low Voltage)
1. Refer to the schematic for the auxiliary heat (usually found in the
air handler unit) and locate the wire(s) that signal the auxiliary heat
to come on. Auxiliary heat usually gets its signal from the thermostat Stage
2 (W2) and/or from the defrost relay.
2. If the thermostat signal and the defrost signal tie together at the
air handler, run a 2-conductor, 18-gauge wire from the control unit to the
air handler unit. If they don't tie together, run a 4-conductor wire to
the control unit from the air handler.
(These wires may be combined with the compressor wires used in the previous
"Hook-up Compressor" section. Generally, you will be safe if you
run a 6-conductor cable from the air handler to the controller to interrupt
the compressor and the auxiliary heat.)
3. Interrupt the signal with the new wires at a point where the thermostat
and defrost tie together. If they don't tie together, interrupt each signal
separately by using four conductors. See diagrams above.
4. Connect the other end of the wires to the appropriate relay. See priority
lists that follow.
Note:
This type of control is usually done in moderate climate regions where there
are usually no more than two 5KW heat strips in the home.
For extremely cold climates or for maximum control, refer to the following section on "Auxiliary
Heat, Individual Elements."

Click on image for a close-up view
Hookup Auxiliary Heat (Individual Elements)
This should be done by a licensed electrician. Not recommended for
homeowners.
1. Turn heat element breaker(s) OFF. This is generally
more than one breaker.
2. Mount a Remote Relay Unit on or near the air handler unit, if required.
(Tech Tip #10 explains Remote Relay Units.)
3. Using 10- or 12-gauge wire as required by breaker size and/or load size, rewire one side of each element through a relay
in the Remote Relay Unit. Wire one element per relay, if possible, leaving the
second, unused relay pole as a spare. If there are five or more elements, wire two elements per relay. (Also
see the instructions that come with the Remote Relay Unit.)
4. Refer to the Remote Relay Unit instructions to wire the Remote Relay
Unit to the control unit.
5. When installation is complete, turn ON breaker(s) to air
handler or electric furnace.
Note
This type of control is usually done in extremely cold regions, or when
individual staging of elements is desired.
Control of Heat Pump:
Example of Priority Hookups
4-Relay Models (Low voltage
control of aux. heat)
|
Last
Shed |
24-hour control |
First Shed |
| Relay |
1 |
2 |
3 |
4 |
| Load |
Dryer |
Compressor |
Water Heater |
Aux.
Heat |
8-Relay Model or 4-RelayModel with Remote
Relay Unit
Auxiliary Heat Individual Elements-Line Voltage Control
|
Last
Shed |
24-hour control |
First Shed |
| Relay |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
| Load A |
Dryer |
Compressor |
Water
Heater |
5KW
Heat |
5KW
Heat |
5KW
Heat |
5-10KW
Heat |
5-10KW
Heat |
| |
|
|
|
|____________________________|
To Remote Relay Unit |
Caution
In extremely cold areas, compressor control is discouraged because of
the excessive stress that results from frequent cold starting.
|