|
Tech Tip #13
Current Transformers
for Demand Controllers
Current transformers are mounted on the incoming electrical service mains
between the utility meter and the main circuit breaker. They are used to
monitor total electrical use, not just loads connected to the Energy Sentry®.
Current transformers generate a current that is proportional to their
turns ratio. This current can be read by the demand controller.
Energy Sentry demand controllers use 1000:1 turns for 200A CTs and 2000:1
turns for 400A CTs. Thus, for 200A CTs, the output of each CT is one one-thousandth
(1/1000th) of an amp, or 1 milliamp, for each ampere that passes through
the mains.
Two CTs are usually mounted inside the load center. Most Energy Sentry
installations use standard CTs that are shipped with each controller. However,
certain installations require special CTs in order to correctly adapt the
Energy Sentry to the electrical service. The CTs must be located so they
monitor the total current of the utility service on which they are installed.
See below for a brief description of the types of CTs available from Brayden
Automation and their proper application.

Click on the Image for a Closer View
Hook-ups
Standard CT
The standard CT will easily fit up to 750 MCM cable (1.17 inches). Be
sure the CT will fit in the load center with the cover in place. If there
is not enough room in the load center, contact your utility company for
the desired installation procedure. Some electrical codes require that CTs
be mounted in a separate enclosure.
1. Turn power OFF. Mount one CT on each of the incoming phase cables
in the load center. Do this by installing the CTs around the main feeder
cables between the meter and the main breaker. Make sure the CTs are mounted
in the same direction.
2. Run the secondary wires to the 4-position terminal strip on the controller
board assembly labeled "J2." Leave about 6 to 8 inches extra.
Do not run leads next to high-voltage (Class 1) wiring if possible.
3. Strip each conductor back 1/4 inch and connect black and white wires
to 4-position terminal strip on the controller board assembly labeled either
"CT1" or "CT2" as follows"
| Terminal # |
Terminal Name |
Wire Color |
| 1 (top) |
CT1 |
White - from CT1 |
| 2 |
CT1 |
Black - from CT1 |
| 3 |
CT2 |
Black - From CT2 |
| 4 (bottom) |
CT2 |
White - from CT2 |
4. Route CT wires around the right side of the controller board assembly.
Route all Class II wiring, including CT wires, throught a separate knockout.
Secure with a cable clamp at the knockout to provide strain relief.
Parallel Feeders
If an electrical service has parallel feeders, you may use two sets of
CTs in parallel if the total input current does not exceed the current rating
of the individual CTs. for example, if you have a 400A service consisting
of two 200A panels and you are using two pairs of 200A CTs, the total current
monitored by both pairs should never exceed 200A. If more than 200A, use
two pairs of 400A CTs. See Tech Tip #14 on
parallel CTs.
400A Large & Extra Large CTs
400A (double-ratio) CTs are designed for services up to 400 amperes.
They also work when there are two service panels of 200A each. Hook up the
secondary just as you hook up the standard CTs. Set the demand range (dr)
to 80 KW for 400A CTs. This will be done automatically at the factory if
400A CTs are ordered with a controller. It can also easily be done in the
field if necessary.
Warning:
Before restoring power to the load center, be sure the secondary wires
are secured to the controller board assembly. Otherwise, the CTs may be
damaged. If the CTs cannot be connected to the controller board assembly,
wire-nut the CT leads together. CTs "Like" a short circuit
they hate an open circuit.
Current Transformers Available from Brayden Automation
& Their Applications
| Type |
P/N (per pair) |
Measurement |
Range |
Dimensions |
| Standard |
8420-3028 |
200A |
48 KW |
2.25 outside diameter (OD), 1.5 inside diameter (ID), 0.5
height (H) |
| Double Ratio Large |
8420-3029 |
400A |
96 KW |
2.75 OD, 1.75 ID, .75H |
| Double Ratio Extra-Large |
8420-3030 |
400A |
96 KW |
3.75 OD, 2.75 ID, 0.5H |
|